9. Press the ENTER key once more to accept the calibration value
A N A L O G O U T P U T
C A L I B R A T E D
10. Analog output signal calibration is complete
11. Press the MENU key three times to exit back to the main operating screen
If you receive the following message:
C U R R E N T D E L T A
O U T O F R A N G E
This indicates that the output current for 0% speed has been set greater than or equal to the output current
setting for 100% speed. Repeat the process and ensure that the 0% calibrated signal is set to a value lower
than the 100% calibrated signal.